INT69 DMY® Motor protector
Functional description:
• When supply voltage is applied, the output relay pulls in after an initialisation period of approx. 3 seconds, provided all thermistors lie below their rated response temperature.
• 1 to 9 PTC thermistors with varied rated response temperatures can be connected in series to the input terminals.
• If any thermistor resistance increases above trip level, the output relay drops out. After cooling down, a 5 minute time delay is activated, during which the relay remains dropped out. After this period has elapsed the relay pulls in again.
• The phase monitoring function is active 1 second after motor start during a 5 second window. Incorrect phase sequence and phase loss results in lockout trip.
• Lockout and time delay can be cancelled by mains reset of approx. 5 seconds.
• To avoid nuisance tripping due to reverse running after shutdown (pressure equalisation), the phase monitoring function is only reenabled approx. 20 seconds after motor stop.
• The relay is fed out as a N/O dry contact, which is closed under good conditions.
• The INT69 DMY is not suitable for use with frequency converters.